Kehua BCS1250K~1725K-B-HUD PCS

PCS unit

1250 kW ~ 1725 kW

  • Online insulation monitoring

    Designed for extreme environmental conditions such as high temperatures, salt loads, extreme cold.

    Full cell condition monitoring and multi-level fire protection.

  • Space-saving, efficient layout

    Smart online updates, easy system maintenance.

    Flexible delivery and fast installation.

  • Supports parallel operation of multiple units and black start

    H/LVRT function (low and high voltage tolerance), high grid adaptability

    Versatile applications such as peak load reduction, frequency regulation and support for grid integration of renewable energy systems

    Inverters authorised in E.on's Hungarian service territory

Kehua BCS1250-1725K-B-HUD Technical Specifications

Technical specifications

BCS1250K-B-HUD BCS1500K-B-HUD BCS1725K-B-HUD
DC input
Max. DC voltage1500 Vdc
DC voltage range1000-1500 Vdc
Max. DC current1403 A1683 A1936 A
Soft startYes
AC output (Mains)
Rated AC power1250 kW1500 kW1725 kW
Max. AC power1375 kVA1650 kVA1897.5 kVA
Rated mains voltage690 Vac 3P3W+PE
Mains voltage range-15%~10% (adjustable)
Network frequency range50 Hz
Max. output current1151 A1381 A1588 A
Performance factor>0.99 (at rated power)
Adjustable power factor1 (inductive) ~ 1 (capacitive)
THDi<3% (névleges teljesítménynél)
AC output (isolated operation)
Rated AC voltage690 Vac
Output voltage accuracy1%
Max. output current1151 A1381 A1588 A
THDu<3% (lineáris terhelés)
Rated output frequency50 Hz
Availability110%
Maximum efficiency99%
General information
Type of isolationNone
IP protectionIP55
Operating temperature-35ºC~60ºC (>45ºC reduced performance)
Relative humidity0~100% (non-condensing)
Cooling typeIntelligent air cooling
Size (W×D×W×M)860×2270×1725 mm
Weight1500 kg
Altitude above sea level4000 m (>2000 m reduced power)
DisplayTouch screen (optional)
Communication protocolModbus RTU, Modbus TCP, IEC61850, IEC104
Communication interfaceRS485, Ethernet
CertificatesIEC/EN 62477-1, EN IEC 61000-6-2/4, EN 50549-2, NC RfG, IEC 62116, IEC 61727